Owned and Operated by Australia's leading Test and Measurement Distributor
TEL: 1800-FLUKE-1 — 1800 358 531
$220.00 .( $242.00 inc. GST )
For all your equipment calibration needs, visit our MyCalibration website.
Free Delivery on orders over $1000
Shipping time may vary for certain products*
If you would like more information regarding this product, simply email us here.
The SEW 890PR Non-Contact Three Phase Sequence and Rotation Tester allows the verification of phase sequence without contacting live terminals
Using non-contact inductive clips that allows the user to simply clip the sensors to the outside of each cable without removing the insulation.
The SEW 890PR is used for detecting clockwise and counterclockwise phase sequence, as well as the presence or absence of phases.
Visual and Audible indicators for clockwise and counterclockwise phase sequence or phase rotation
● The 890 PR is a Non-Contact phase detector with flashing LEDs and a beeping buzzer to show the detection of AC 3-phase sequence.
● Two functions in one unit : open phase & phase sequence detection.
● Convenient brightness switch to make the indication visible in dim areas or sunlight.
● Back cover magnets which attach the instrument to the AC distribution panel offer easy measurement.
● 3-Phase AC 70 to 1000V is fitted for detection.
● Conductor size: 1~35mm
● Detect frequency range is from 45 to 65Hz.
● CAT III 1000V / CAT IV 600V Safety Rating
The SEW 890PR Non-Contact Three Phase Rotation and Sequence Tester has the ability to measure without contacting any live parts. The user simply clamps the three clamps onto each cable over the insulation and reads the status by way of the adjustable intensity LED’s, allowing either indoor or outdoor use. On switch on the SEW 890PR will perform an LED status test to ensure all LED’s are functioning correctly before use and it will power off after 5 minutes if not connected to a live circuit.
Once the SEW 890PR’s clamps are connected to the corresponding cables, the SEW 890PR will automatically display the presence of three phases on the three “power on” LED’s and will also display the direction of phase rotation with a clockwise or counterclockwise LED and a phase rotation map, showing the phase sequence.
An audible buzzer signals the user with an intermittent tone for clockwise rotation, and a continuous tone for counterclockwise (incorrect) rotation. The SEW 890PR has four built in magnets, located on the rear of the instrument to allow for it to be held on a metal surface (switchboard door etc.)to enable handsfree use.
Measurement principle | Static induction | |
Input voltage | 70~1000Vac | |
Frequency range | 45-65Hz | |
Auto-off | 5 min. after power on without detection | |
Low battery warning | Power LED flashes at 4.6±0.1V or less |
|
Operating temperature & humidity |
0°C ~ 40°C Max. 80% R.H. | |
Storage temperature & humidity |
-10°C ~ 50°C Max. 80% R.H. | |
Cable length | Approx. 800mm | |
Dimensions | 115(L) × 65(W) × 40(D)mm | |
Weight (battery included) | Approx. 370g | |
Power source | 1.5V (AA) × 4 Alkaline batteries | |
Safety standard | EN 61010-1 CAT III 1000V / CAT IV 600V EN 61326-1 EN 61557-1 EN 61557-7 |
Weight | .25 kg |
---|