The Kyoritsu 6010B can perform loop and RCD testing. This includes testing across a large range of currents (10/30/100/300/500 mA) and an auto ramp function. The Kyoritsu 6010B also features a built memory to store up to 300 measured results. The results can be downloaded to PC using the optional communication adaptor and “KEW Report” PC software.
The Kyoritsu 6010B is supplied with test leads, case, shoulder strap and batteries.
Kyoritsu 6010B Features:
• Continuity:20/200Ω 200mA Test Current
• Insulation: 500/1000V, 20/200MΩ 1mA Rated Test Current
• Loop Impedance:20/2000Ω 15mA Test Current at 2000Ω (No RCD Trip)
• RCD:10/30/100/300/500mA x1/2, x1, Fast Trip(40ms), DC, Auto Ramp
• Test of a large kind of RCD’s:Standard, Selective, AC and A(DC sensitive breakers)
• Uc(Contact Voltage): 100V
• Designed to IEC 61010-1, IEC 61557
• Data Memory:300 measured results
• The stored data can be transferred to PC via Optical Adaptor Model 8212-USB or 8212-RS232C.
Kyoritsu 6010B Multifunction Tester Specifications:
Continuity Testing | ||
---|---|---|
Measuring Range | 20/200Ω (Auto-Ranging) | |
Open Circuit Voltage | > 6V | |
Short Circuit Current | > 200mA | |
Accuracy | ±(3%rdg + 3dgt) | |
Insulation Resistance Testing | ||
Measuring Range | 20/200MΩ (Auto-Ranging) | |
Test Voltage | 500/1000V | |
Open Circuit Voltage | +20% – 0% | |
Rated Current | > 1mA | |
Accuracy | ± (3%rdg + 3dgt) | |
Loop Impedance Testing | ||
Impedance Range | 20/2000Ω | |
Rated Voltage | 230V + 10% – 15%(50Hz) | |
Normal Test Current | 20Ω:25A/10ms 2000Ω:15mA/350ms max. |
|
Accuracy | ±(3%rdg + 8dgt) | |
RCD Testing | ||
Test Current (Test Current Duration) |
x1/2, x1 | 10, 30, 100, 300, 500mA (2000ms) |
Fast | 150mA (50ms) | |
DC | 10, 30, 100, 300mA (2000ms), 500mA (200ms) | |
Auto Ramp | Goes up by 10% from 20% to 110% of IΔn. 300ms×10 | |
Rated Voltage | 230V + 10% – 15% 50Hz | |
Accuracy | Test Current | x1/2: -8%-2% x1, FAST: +2%+8% DC: ±10% Auto Ramp: ±4% |
Trip Time | ±(1%rdg + 3dgt) | |
Uc Testing | ||
Measuring Range | 100V | |
Rated Voltage | 230V + 10% – 15% (50Hz) | |
Test Current | 5mA at IΔn = 10mA 15mA at IΔn = 30/100mA 150mA at IΔn = 300/500mA |
|
Accuracy | +5% to +15%rdg±8dgt |
Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2 IEC 61557-1, 2, 3, 4, 6, 10, IEC 60529 (IP40) |
---|---|
Power source | R6 or LR6 × 8 |
Dimensions | 115(L) × 175(W) × 86(D)mm |
Weight | 840g approx. |
Included Accessories | 7122B (Test leads) KAMP10* (Test Lead with IEC Connector) Pouch for Test leads Shoulder Strap Shoulder Pad Instruction Manual |
Optional Accessories | 7133B (Distribution board test leads) 8212-RS232C (RS232C adaptor with “KEW Report (Software)”) 8212-USB (USB adaptor with “KEW Report (Software)”) |
Tim Smith (verified owner) –
Easy to order, Good prices and Prompt Delivery! Too Easy! Good meter, Kyoritsu standard. Does what it says well.