Measurement of the earth electrode resistance
(3-Pole method)
The international standard IC 60364-6 provides information regarding the measurement of the resistance of an earth electrode for TT, TN and IT systems.
This measurement shall be made by the Volt-Amperometric method using two auxiliary earth electrodes. The instrument that covers this requirement is the Earth Tester.
Measurement of the simplified earth resistance
(2-Pole method)
Kyoritsu 4105DL Earth Tester Features:
• 3 pole and 2 pole Earth Resistance measurement (0.01Ω-2000Ω)
• Waterproof design (IP67)
• Rotary Switch makes the user interface very intuitive
• Large LCD Display with Backlight
• Led to monitor correct / non correct auxiliary earth spike resistance
• Earth Voltage Measurement (AC/DC 0-300V)
• CAT Ⅳ – 100V
Specifications
Earth resistance
measurement |
20Ω |
200Ω |
2000Ω |
|
Measuring range |
0.00 – 2000 Ω |
Display range |
0.00 – 20.99 Ω |
0.0 – 209.9 Ω |
0 – 2099 Ω |
Accuracy*1 |
±1.5%rdg±0.08 Ω*2 |
±1.5%rdg±4dgt |
Auxiliary earth resistance*3 |
<10kΩ |
<50kΩ |
<100kΩ |
Comparator reference value |
10Ω |
100Ω |
500Ω |
Earth voltage measurement |
|
Measuring range |
0 – 300 V AC (45 – 65Hz) |
±0 – ±300 V DC |
Display range |
0.0 – 314.9 V |
0.0 – ±314.9 V |
Accuracy |
±1%rdg±4dgt |
Overload protection |
Earth resistance : 360V AC (10 seconds) |
Earth voltage : 360V AC (10 seconds) |
Applicable Standards |
IEC 61010-1, CAT IV 100 V /CAT III 150 V /CAT II 300 V Pollution degree 3 |
IEC 61010-2-030,IEC 61010-031, IEC 61557-1, -5 |
IEC 60529 IP67, IEC 61326-1, -2-2, EN50581(RoHS) |
Power source |
LR6(AA)(1.5V) × 6 |
Dimensions |
121(L) × 188(W) × 59(H) mm (including case lid) |
Weight |
Approx. 690g (including batteries and case lid) |
Accessories
for 4105DL |
7127B(Simplified measurement probe) |
8041(Auxiliary earth spikes[2 spikes/1set]) |
9121(Shoulder strap) |
7267(Cable reel for Earth resistance tester (red)) |
7268(Cable reel for Earth resistance tester (yellow)) |
7271(Earth resistance test leads) |
9190(Carrying case) |
LR6(AA) × 6, Instruction manual |
Accessories
for 4105DL-H |
7127B(Simplified measurement probe) |
8041(Auxiliary earth spikes[2 spikes/1set]) |
9121(Shoulder strap) |
7266(Earth resistance test leads[red-20m, yellow-10m, green-5m/1set]) |
9191(Hard case) |
LR6(AA) × 6, Instruction manual |
Optional |
7272(Precision measurement Cord set) |
8259(Adapter for measurement terminal) |
*1 For precision measurement, auxiliary earth resistance should be 100 Ω ±5% or less.
*2 At simplified measurement add ±0.10 Ω to the specified accuracy.
*3 Accuracy within the auxiliary earth resistance: ±5% rdg ±10 dgt.
Reviews