The Fluke 1664 FC Installation Multifunction Testers are designed to quickly and efficiently test to all local regulations, protect appliances, and share test results in real time over your smartphone. With the included “Insulation Pre-test,” you can simply and easily detect when appliances are connected to the system and stop the test, if needed. Additionally, the Auto Test feature runs seven installation tests automatically in one sequence – with just a single connection. Plus, with Fluke Connect Measurements, you can share your test results in real time via your smartphone – making it easier than ever to keep everyone on the same page.
PROMO – FREE FEV300 EV Charging Adaptor available with ONLINE PRICING ONLY
Fluke 1664 FC Multifunction Installation Tester helps expedite installations
The Fluke 1664 FC is a powerful multifunction tester that helps you quickly and efficiently test to all local regulations, protect appliances, and share test results in real time over your smartphone.
Protect appliances from accidental damage
The Fluke 1664 FC installation multifunction tester is the only one of its kind with “Insulation PreTest.” This amazing feature stops the insulation test and provides a visual warning if it detects that an appliance is connected to the system under test. With the Fluke 1664 FC, you’ll never have to worry about causing expensive or damage to your customers’ peripheral equipment.
Auto Test reduces test time
Auto Test performs up to seven installation tests in one sequence, reducing the number of manual connections and the possibility of errors. This tester also reduces test time, so you can get the job done quickly and efficiently.
Save time and enhance collaboration
With its built-in Fluke Connect® capability, the 1664 FC allows you to send test results to your smartphone, save them to the cloud, and share measurements in real time with team members through a ShareLive video call. This is the fastest way to let your team see what you see, and to help you get approvals without leaving the field.
Retrieve stored results from anywhere
With Fluke Cloud™ storage, you can easily retrieve stored results whether you’re in the office or in the field. This way, you can make decisions in real time. In addition, the data protection is world-class, and you can import the data into Fluke DMS (Data Management Software) to process and generate certificates.
Other helpful features:
Weight | 1.5 kg |
---|
AC voltage measurement | ||
Range | 500 V | |
Resolution | 0.1 V | |
Accuracy 45 Hz – 66 Hz | 0.8% + 3 | |
Input impedance | 360 kΩ | |
Overload protection | 660 V rms | |
Continuity testing (RLO) | ||
Range (autoranging) | 20 Ω / 200 Ω / 2000 Ω | |
Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |
Open Circuit Voltage | >4 V | |
Insulation resistance measurement (RISO) | ||
Test voltages | 50-100-250-500-1000 V | |
Accuracy of tTest voltage (at rated test current) | +10%, -0% | |
Test voltage | 50 V 100 V 250 V 500 V 1000 V |
|
Insulation resistance range | 20 MΩ /50 MΩ 20 MΩ / 100 MΩ 20 MΩ / 200 MΩ 20 MΩ / 200 MΩ / 500 MΩ 20 MΩ / 200 MΩ / 1000 MΩ |
|
Resolution | 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ |
|
Test current | 1 mA @ 50 kΩ 1 mA @ 100 kΩ 1 mA @ 250 kΩ 1 mA @ 500 kΩ 1 mA @ 1 MΩ |
|
Loop and line impedance (ZI) | ||
Range | 10 Ω / 0.001 Ω / High current mΩ mode | |
Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |
Prospective earth fault current, PSC test | ||
Range | 1000 A / 10 kA (50 kA) | |
Resolution | 1 A / 0.1 kA | |
Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. | |
RCD testing, RCD types tested | ||
RCD Type | AC¹ G²,S³ |
|
Model 1664 | A, AC, B5, S | |
Notes | ¹Responds to AC ²General, no delay ³Time delay 4Responds to pulsed signal 5Responds to smooth DC signal |
|
Tripping speed test (ΔT) | ||
Current settings¹ | 10-30-100-300-500-1000 mA – VAR 10-30-100 mA |
|
Multiplier | x ½, x 1 x 5 |
|
Measurement range | RCD Type G | 310 ms 50 ms |
RCD Type S | 510 ms 160 ms |
|
Notes | ¹1000 mA type AC only 700 mA maximum type A in VAR mode VAR mode not available for type B. |
|
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN) | ||
Current range | 30% to 110% of RCD rated current¹ | |
Step size | 10% of IΔN² | |
Dwell time | Type G | 300 ms/step |
Type S | 500 ms/step | |
Measurement accuracy | ±5% | |
Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC 35% to 140% for Type A (>10 mA) 35% to 200% for Type A (≤10 mA) 50% to 200% for Type B ²5% for Type B |
|
Notes | ¹30% to 150% for Type A IΔN > 10 mA 30% to 210% for Type A IΔN = 10 mA 20% to 210% for Type B |
|
Earth Resistance Test (RE) | ||
Range | 200 Ω / 2000 Ω | |
Resolution | 0.1 Ω / 1Ω | |
Frequency | 128 Hz | |
Output Voltage | 25 V | |
Phase Sequence Indication | ||
Icon | ![]() |
|
General Specifications | ||
Size (L x W x H) | 10 x 25 x 12.5 cm | |
Weight (incl. batteries) | 1.3 Kg | |
Battery size, quantity | Type AA, 6 ea. | |
Sealing | IP-40 | |
Safety | Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition | |
Overvoltage | CAT III / 500V; CAT IV 300V | |
Performance | EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition |