    Features

    • EXTECH 382357 Clamp-on Ground Resistance Tester
    • Autoranging ground resistance measurements from 0.025Ohm to 1500Ohm with 0.002Ohm resolution
    • True RMS AC Leakage current range of 0.2mA to 30A with 1.000mA resolution
    • Programmable Datalogging with 116 data points
    • Programmable Hi/Lo Alarm
    • 0.9″ (23mm) Jaw size for large ground rods

     

    ce     CATII-600V     CATIII-1000V     warranty12

    Authorised Australian Distributor.

     

    SKU: EXTECH 382357 Categories: , Tag:

    Extech 382357 Clamp-on Ground Resistance Tester.

    Clamp-On Ground Resistance Tester

    The Extech 382357 Clamp-on Ground Resistance tester enables non-contact measurements of ground conductors without the need for auxiliary ground spikes. Comes with 9V battery, resistance check plate, metal storage case, and user manual.

    Additional Features

    Measures resistance from 0.03Ω to 1500Ω and True RMS AC Leakage current from 0.2mA to 30.00A. It features programmable datalogging with 116 points, programmable hi/lo alarms, 0.9” jaw size, self-calibration when powered on, and verification resistors to confirm the accuracy of the meter. Cat III-300V.

    Applications

    Clamp-On Ground Tester simplifies ground resistance measurements on multiple-point ground systems. Use to verify the resistance of cellular and communication tower ground grids, check utility transmission systems and grounding rods, perform maintenance on electrical transportation systems. Ideal for verifying ground systems in sub-stations, factories, and office buildings.

    Applications:

    • Verify resistance of cellular and communication tower ground grids
    • Check utility transmission systems and grounding rods
    • Maintenance on electric transportation systems
    • Ideal for grounding systems in sub-stations, factories and office buildings
    Resistance Test Frequency 1.667KHz (15mV rms approx.)
    Max Conductor size 0.9” (23mm)
    Display 4-digit (9999 count) display
    Sampling rate 0.4 seconds
    Power supply One 9V battery
    Power consumption 40mA
    Temp. Coefficient 0.15 times the specified accuracy per degree centigrade from 4 to 18°C and 28 to 50°C
    Current Overload Protected to 100A Continuous, 200A for less than 60 seconds (50/60Hz)
    Continuity check Audible tone if reading is less than approx. 40 Ω
    Range selection Automatic ranging
    Safety Meets the requirements for IEC1010-1 Category III 300V and Category II 600 V
    Operating conditions -20 to 50°C with < 85% RH
    Storage conditions -28 to 60°C with < 75% RH
    Dimensions 258 x 110 x 47mm
    Weight 700g
    Accessories Resistance check plate, 9V battery, carrying case
    Weight 3 kg

    Reviews

    There are no reviews yet

    Be the first to review “EXTECH 382357 Clamp-on Ground Resistance Tester”

    Need help? Call our support team 1800 358 531

    • Place The Order and Earn Points Earn 10 Points on every AUD $100.00 spent
    • Write Review
      Write reviews and earn 300 Point
    • image
      Apply Points on Cart Total

      Conversion Rule : AUD $10.00 = 500 Point

    Check your point total now Check your point total now